Numeric sensor [NumericSensorElementName] going high (upper critical) has
asserted. (Mezz Card Temp)
This message is for the use case when an implementation has detected an
Upper Critical sensor going high has asserted.
May also be shown as
800109012c01ffff or 0x800109012c01ffff
Alert Category
Critical - Temperature
CIM Information
Prefix:PLAT
and ID:0494
Automatically Notify Support
No
User Response
- Make sure there is a node filler correctly installed for the empty node slot.
- Make sure the air baffles are placed and correctly installed; and make sure the node cover is installed and completely closed.
- Make sure the fans are operating, and there are no obstructions to the airflow (both front and rear of the server).
- Reduce the Ambient temperature. The system must be operating within the specifications. (see Features and specifications for more information)