Numeric sensor [NumericSensorElementName] going high (upper non-recoverable)
has asserted. (CPU1 VR Temp VCO)
This message is for the use case when an implementation has detected an
Upper Non-recoverable sensor going high has
asserted.
May also be shown as
80010b010703ffff or 0x80010b010703ffff
Alert Category
Critical - Temperature
CIM Information
Prefix:PLAT
and ID:0498
Automatically Notify Support
No
User Response
- Make sure there is a node filler correctly installed for the empty node slot.
- Make sure the air baffles are placed and correctly installed; and make sure the node cover is installed and completely closed.
- Make sure the fans are operating, and there are no obstructions to the airflow (both front and rear of the server).
- Reduce the Ambient temperature. The system must be operating within the specifications. (see Features and specifications for more information)