80070301-1103ffff : Sensor [SensorElementName] has transitioned to non-recoverable from a less severe state. (PCI 3 Temp)

Sensor [SensorElementName] has transitioned to non-recoverable from a less severe state. (PCI 3 Temp)

This message is for the use case when an implementation has detected a Sensor transitioned to non-recoverable from less severe.

May also be shown as 800703011103ffff or 0x800703011103ffff

Severity

Error

Alert Category

Critical - Temperature

Serviceable

Yes

CIM Information

Prefix:PLAT

and ID:0524

SNMP Trap ID

0

Automatically Notify Support

No

User Response

  1. Make sure there is a node filler correctly installed for the empty node slot.
  2. Make sure the air baffles are placed and correctly installed; and make sure the node cover is installed and completely closed.
  3. Make sure the fans are operating, and there are no obstructions to the airflow (both front and rear of the server).
  4. Reduce the Ambient temperature. The system must be operating within the specifications. (see Features and specifications for more information)
  5. Make sure the PCI adapter is supported by the server. To confirm, see the IBM ServerProven website.
  6. Replace the PCI adapter and make sure the PCI adapter is functioning normally.